Stop a chlorine-cylinder leak at a treatment plant
Reinforce the Chlorine Institute Kit A/B order. Evacuate and approach from upwind, orient the cylinder so gas not liquid escapes, and do not spray water on the leak.
- Evacuate occupants upwind or crosswind.
- Don the supplied-air or SCBA ensemble before approaching.
- Approach from upwind with Emergency Kit A or B.
- Orient the cylinder so gas, not liquid, escapes.
- Apply the matching kit device to the leak.
- Do not spray water on the leak.
- Notify the LEPC / fire department and the taught agency.
- Do not return the cylinder to service; isolate it for the supplier.