Place a fire-alarm system on impairment
Reinforce the NFPA 72 impairment order from facility-fire training. Detectors are not taken out of service until the fire watch and required notifications are in place.
- Determine the impairment scope and expected duration.
- Notify the monitoring station, AHJ, and site emergency contacts as required.
- Establish the compensatory fire watch before devices are disabled.
- Tag the impaired panel or devices.
- Disable only the approved devices.
- Restore the system at the end of the work.
- Test the restored devices for correct operation.
- Notify the monitoring station and AHJ that the impairment is ended.